Hastings 7707 Digital 100KV Hot Stick Tester with Calibration Certificate

$2,295.00
Mitchell Part Number
HFP-7707
Manufacturer
Availability
Typically in stock, Call if Urgent
Quick overview

Hastings 7707 Digital Hot Stick Tester indicates leakage values that would be present in a hotstick at 75kV/ft (wet) /100kV/ft (dry) in accordance with OSHA 1910.269. Designed for portability. 




  • Sticks can be tested at jobsite if no power is present.
  • Test hot sticks wet or dry. The tester has a selector switch for wet or dry testing and a dual range scale which gives the operator leakage current values in micro amps.
  • Utilizing a 2,500 volt output, the meter is calibrated to indicate the leakage values that would be present if 75KVAC were applied to a 12” section of the fiberglass tool for the wet test and 100KVAC per foot for the dry test.
  • Portable and lightweight for ease of use. The tester is designed to protect the operator while in use.
  • The tester comes complete with a padded carrying case and directions for proper use.
  • A test bar is also provided to ensure the tester is working properly.
  • Battery Life - estimate 6 hours of continuous testing at 70 degrees.
  • Charge Time - estimate 4 hours.
  • Bright Digital Display with easy to read Pass/Fail.
  • If battery is dead, this can run on standard 110 volt outlet.
More Information
Weight 15.000000
Product Includes tester, test bar, usb charging cord, calibration certificate and carrying case
Specifications
  1. Select either the “WET TEST” or  “DRY TEST” position on the switch appropriate to the type of test you  intend to perform.
  2. Rotate the “ZERO” knob until the meter indicator is aligned with the zero position on the display.
  3. For ‘Wet’ Test, spray the entire stick with DISTILLED water to thoroughly wet the surface. Spray the water uniformly on the pole until droplets just begin to drip from the bottom surface. 
  4. Move in six inch increments along the length of the stick.

Wet Test Results: Current industry standards require a  stable or decreasin greading which  would also eliminate flashovers. Our recommendation is that no readings over 75 micro Amperes are acceptable  for the wet test. This is more stringent than the current industry standards and is well below the level where flashover or unstable readings will occur. 

Power Supply Internal rechargeable batteries or 110V AC outlet
Manufacturer Hastings
MPN 7707
You're reviewing: Hastings 7707 Digital 100KV Hot Stick Tester with Calibration Certificate
Your Rating