- 275HVD
- AC High Voltage Detector
- AC Voltage Detector
- High Voltage Detector
- Insulated Screwdriver
- Insulated Screwdriver Set
- Insulated Screwdrivers
- Insulated Tool Kit
- Insulated Tool Set
- Insulated Tools
- Klein Insulated Screwdriver
- Klein Insulated Tools
- Klein Screwdrivers
- Non Contact High Voltage Detector
- Non Contact Voltage Detector
- aemc
- fluke
- megohmmeter
- multimeter
- tsi
Arc Flash Protection
Arc Flash Protection Information
What is an Arc Flash?
An arc flash is a voltage breakdown of the resistance of air resulting in an arc which can occur where there is sufficient voltage in an electrical system and a path to ground or lower voltage.
Example:
Arc flash incidents are highly improbable on systems operating at less than 208 volts phase to phase (120V to ground) when fed by less than a 125 kV·A transformer. 120 volts does not provide sufficient energy to cause an arc flash hazard. Most 480 V electrical services have sufficient capacity to cause an arc flash hazard. Medium-voltage equipment (above 600 V) is higher energy and therefore a higher potential for an arc flash hazard.
Arc Flash PPE:
With recent increased awareness of the dangers of arc flash, there have been many companies that offer arc flash PPE. The fabrics or materials are tested for their arc rating. The arc rating is the maximum incident energy resistance demonstrated by a material prior to breakopen or at the onset of a second-degree skin burn. Arc rating is normally expressed in cal/cm2 (or small calories of heat energy per square centimeter). The tests for determining arc rating is defined in ASTM F1506 Standard Performance Specification for Flame Resistant Textile Materials for Wearing Apparel for Use by Electrical Workers Exposed to Momentary Electric Arc and Related Thermal Hazards.
Selection of appropriate PPE, given a certain task to be performed, is normally handled by one of two possible ways. The first method is to consult a hazard category classification table, like that found in NFPA 70E. Table 130.7(C)(9)(a) lists a number of typical electrical tasks are various voltage levels and recommends the category of PPE that should be worn. For example when working on 600 V switchgear and performing a removal of bolted covers to expose bare, energized parts, the table recommends Category 3 Protective Clothing System. This Category 3 system corresponds to an ensemble of PPE that together offers protection up to 25 cal/cm2. The minimum rating of PPE necessary for any category is the maximum available energy for that category. For example, a Category 3 arc-flash hazard requires PPE rated for no less than 25 cal/cm2.
The second method of selecting PPE is to perform an arc flash hazard calculation to determine the available incident arc energy. IEEE 1584 provides a guide to perform these calculations given that the bolted fault current, duration of faults, and other general equipment information is known. Once the incident energy is calculated the appropriate ensemble of PPE that offers protection greater than the energy available can be selected.
PPE provides protection after an arc flash incident has occurred and should be viewed as the last line of protection. Reducing the frequency and severity of incidents should be the first option and this can be achieved through a complete arc flash hazard assessment and through the application of technology such as high resistance grounding which has been proven to reduce the frequency and severity of incidents.
The Key Factors in Determining Arc Flash:
Fault current
Fault current can be limited by using current limiting devices such as grounding resistors or fuses. If the fault current is limited to 5 amperes or less, then many ground faults self-extinguish and do not propagate into phase-to-phase faults.
Arcing time
Arcing time can be reduced by temporarily setting upstream protective devices to lower setpoints during maintenance periods or by employing zone interlocking (ZSIP).
Arcing time can significantly be reduced by protection based on detection of arc-flash light. Optical detection is often combined with overcurrent information. Light and current based protection can be set up with dedicated arc-flash protection relays or by using normal protection relays equipped with arc-flash option.
The most efficient means to reduce arcing time is to use an arc eliminator that will extinguish the arc within a few milliseconds.
Distance
Remote operators or robots can be used to perform activities that are high risk for arc flash incidents like racking breakers on a live electrical bus. The distance from an arc flash source within which an unprotected person has a 50% chance of receiving a second degree burn is referred to as the "flash protection boundary". Those conducting flash hazard analyses must consider this boundary, and then must determine what PPE should be worn within the flash protection boundary.







Loading...