SMC Raptor C05 Primary Injection Circuit Breaker High Current Test System with remote app control (tablet not included)

SMC Raptor C05 Primary Injection Circuit Breaker High Current Test System

Automatic Output Regulation
DSP technology maintains a uniform current waveform even with changing load impedances.
Speeds testing by eliminating the manual variac. Every other high current system requires user to
manually set output current.
Overcomes heating of the trip element which caused the current to drop during test.
Weight and Size
Amazing portability compared to other existing equipment, due to its light weight and small size,
that allows one person to carry it, even in his own car.
Easier and cheaper to transport and handle. Each unit has wheels and folding handle.
Reduces the length of cables required as sets can be much closer to the device tested.
Facilitates portability into installations with limited space and/or with difficult access, such as
stairs, soft soils, underground substations, etc.
Multi-Functionality
The Raptor system concentrates many applications and testing assets, offering a time-saving and
cost effective solution.
The Raptor logic system features high-power processors to take care of future requirements, and
their functionality can be readily enhanced by means of firmware upgrades through internet.
Expandability
The modular design can accommodate several Raptor Slaves to the Master unit, and user is not
limited to initial power requirement, being able to upgrade the system at a modest cost for higher
power needs.
Sets are immediately assembled and synchronized thanks to infrared technology connectivity, IRDA
type, thus saving time, making the portability even better, and the expandability of the system a
simple task.
Loop-through concept
The Loop-through high current secondary concept contributes both to the flexible modularity and to
the lightness and smallest size of the Raptor.
Unique capacity to adjust the voltage and current required through the number of loop turns used.
Reduces cables connection to the minimum possible, thus reducing power losses, and simplifying
the test process.
Remote Control (Tablet not included)
Wifi adapter allows use of users own phone, tablet or PC along with free App download to control unit
Simplify testing through a automating process and test templates, including the storage of test
results, and reducing testing time, with a easy to use Test Management.
Pre-defined test templates help the user to perform quickly and in a more efficient way the
most frequent tests, with minimal training and preparation. Users can also create their own test
templates.
Ethernet connector for software updates.
Reliable high speed Raptor Bus connector, with failure detection and alarms.
On screen calculations and magnitudes conversions.
User´s assistance for system configuration, cable selection and testing.
Measurement section
Voltmeter, Ammeter and Low signal Voltmeter inputs, measures AC and DC signals with phase
meter incorporated, extending the testing performance.
Binary input, voltage or dry contact, to detect trip commands that define the end of some tests.

 

Master Unit Features:

Regulated high current output. Able to inject up to 3.8kA (with 3kVA) indefinitely or 9.5kA (with 2kVA) during 3s using a single turn. In the case of being N turns the injecting current will be divided by N but power will be maintained. Each Slave unit adds nearly twice the power generated by the Master unit. These systems will be able to inject up to 15kA during 3s.

Regulated auxilliary output. Working in current mode is capable of injecting up to 9 A indefinitely or 35A for 3s and it is regulated by primary. Working in Voltage mode is capable of generating voltage up to 200V

Voltmeter Input. Ranges: 0.2, 2, 20 or 300Vac/dc (auto or manual). Built-in phase angle meter.

Ammeter input. Ranges: 0.2, 2 or 20Aac/dc (auto or manual). Built-in phase angle meter.

Low signal Voltmeter. Ranges: 30, 300 or 3000 mVac/dc (auto or manual). Built-in phase angle meter.

Binary input. Voltage or dry contact

LEDs: Report on certain states of the unit: overload, temperature, status of communications, standby, digital input status indicators, power outputs and supplied unit status.

IRDA interfaces: Connects Raptor-SL units, one with each other, and / or the Master Raptor-MS.

More Information
Weight 80.000000
Product Includes one master unit (power cord, low voltage cable, cal cert, nylon bag), USB cable, power adapter and manual)
Specifications

RAPTOR-MS
(values @240 Vac, 50 Hz, 1 turn sec. 960 mm2, measured 25 cm on each side)
HIGH CURRENT OUTPUT
Output Current Output Voltage
No Load V (0%Imax) 0 - 1.20 Vac - Continuous
3.8 KAac (30%Imax) 0 - 0.81 Vac - Continuous
7.5 KAac (60%Imax) 0 - 0.42 Vac - 3 min
13 KAac (Imax) 0 - 0.22 Vac - 3 s
No Load Resolution 25 uVac
Output Frequency 20 - 400 Hz (Power reduction applied at 50 > f > 60 Hz)
LOW CURRENT OUTPUT (Not simultaneous with high current output)
Output Current 0 - 35 Aac (0 – 9 Aac continuous)
Voltage Output 0 - 200 Vac
Output Frequency 20 - 400 Hz (Power reduction applied at 50 > f > 60 Hz)
Isolated output Yes
Protection fuse
MEASUREMENTS
Secondary Current (for high current output)
Ranges 0 - 1 / 0 - 15 KAac
Resolution 1 Aac, 10 Aac
Accuracy ±0.2% of the value ±0.2% of the range
Phase angle ±0.25º
Ammeter/Low Level Voltmeter
Ammeter Ranges 0 - 0.2 / 0 - 2 / 0 - 20 Aac
Ammeter Resolution 0.1 mAac, 1 mAac, 10 mAac
Ammeter Impedance <10 mΩ
Voltmeter Ranges 0 - 30 mVac, 0 - 0, 3 Vac, 0 - 3 Vac
Voltmeter Resolution 0.015 mVac, 0.15 mVac, 1.5 mVac
Voltmeter Impedance >3000 KΩ
Frequency range 20 - 400 Hz
Accuracy ±0.1% of the value ±0.1% of the range
Phase angle ±0.25º
Isolated input Yes
Voltmeter
Ranges 0 - 0.2 / 0 - 2 / 0 - 20 / 0 - 300 Vac
Resolution 0.1 mVac, 1 mVac, 10 mVac, 0.15 Vac
Impedance >120 KΩ
Frequency range 20 - 400 Hz
Accuracy ±0.1% of the value ±0.1% of the range
Phase angle ±0.25º
Isolated input Yes
Binary Input
Type Dry contact / Voltage
Voltage mode Levels 1.5 V, 15 V
Time resolution 1 ms
Max. Voltage 250 Vac
Isolated input Yes
COMMUNICATIONS
2 RS-485 Raptor Bus connectors to control unit Raptor-HH and/or other units
2 IrDA interfaces Two channels for master/slaves linking

size 21.5" x 17.5" x 9" (77 lbs)
Power Supply 208-240 VAC 50/60hz
Manufacturer SMC
MPN RAPTOR C05
Manufacturer Warranty 1 Year
You're reviewing: SMC Raptor C05 Primary Injection Circuit Breaker High Current Test System