FLUKE 1587 FC Insulation Multimeter with Fluke Connect

Special Price $987.04 Regular Price $1,038.99
Mitchell Part Number
JF-4691215
Manufacturer
Availability
Typically in stock, Call if Urgent
Quick overview
FLUKE 1587 FC Insulation Multimeter with Fluke Connect

FLUKE 1587 FC Insulation Multimeter with Fluke Connect

The Fluke 1587 FC Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.

The Fluke 1587 FC Insulation Multimeter adds four powerful new diagnostic functions through the Fluke Connect® Measurements app:

  • PI/DAR timed ratio tests with TrendIt™ graphs identifies moisture and contaminated insulation problems faster
  • Memory storage through Fluke Connect eliminates writing down results, reduces errors and saves data for historical tracking over time
  • Temperature Compensation through app for establishing accurate baselines and relevant historical comparisons
  • Historical tracking and trending of assets identifies degradation over time, allows real-time decisions to be made in the field with Fluke Connect® Assets

Product highlights

  • PI/DAR timed ratio tests
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • VFD low-pass filter for accurate motor drive measurements
  • Auto-discharge of capacitive voltage for added user protection
  • Insulation test (1587 FC: 0.01 MΩ to 2 GΩ)
  • Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V) for many applications
  • AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (Ω), Continuity
  • Capacitance, diode test, temperature, Min/Max, frequency (Hz)
  • Auto power off to save battery power
  • CAT III 1000 V, CAT IV 600 V measurement category
  • Large display with backlight
  • Rugged, utility hard case allows you to bring everything you need for the job
  • Included accessories: Remote probe, test leads and probes, alligator clips, K-type thermocouple
  • Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient hands free operation
  • Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase
More Information
Weight 4.900000
Product Includes Insulation Multimeter, Remote probe, Test leads, Alligator clips, K-type thermocouple, Hard case, Four AA alkaline batteries, Quick Reference Guide, CD Rom with Manual
Specifications

AC voltage measurement
Range
600.0 mV     Resolution     0.1 mV
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)     ±(2% + 3)
6.000 V     Resolution     0.001 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)     ±(2% + 3)
60.00 V     Resolution     0.01 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)     ±(2% + 3)
600.0 V     Resolution     0.1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)     ±(2% + 3)¹
1000 V     Resolution     1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(2% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)     ±(2% + 3)¹
¹ 1 kHz bandwidth
Low-Pass Filter Voltage
Range
600.0 mV     Resolution     0.1 mV
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)     +(2% + 3), -(6% - 3)
6.000 V     Resolution     0.001 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)     +(2% + 3), -(6% - 3)
60.00 V     Resolution     0.01 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)     +(2% + 3), -(6% - 3)
600.0 V     Resolution     0.1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)     +(2% + 3), -(6% - 3)
1000 V     Resolution     1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)     ±(2% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)     +(2% + 3), -(6% - 3)
DC Voltage Measurement
Range     Resolution     Accuracy ±(% of Rdg + Counts)
6.000 V dc     0.001 V     ±(0.09% + 2)
60.00 V dc     0.01 V     ±(0.09% + 2)
600.0 V dc     0.1 V     ±(0.09% + 2)
1000 V dc     1 V     ±(0.09% + 2)
Input impedance      10 MΩ (nominal), <100 pF
Normal mode rejection ratio      >60 dB @ 50 Hz or 60 Hz
Common mode rejection ratio      >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance)
Accuracies apply to ± 100% of range
DC Millivolts Measurement
Range     Resolution     Accuracy ±(% of Rdg + Counts)
600.0 mVdc     0.1 mV     ±(0.1% + 1)
DC and AC Current Measurement
AC 45 Hz to 1000 Hz
Range     400 mA
Resolution     0.1 mA
Accuracy ±(% of Rdg+Counts)     ±(1.5% + 2)¹
Burden voltage (Typical)     2 mV/mA
Range     60 mA
Resolution     0.01 mA
Accuracy ±(% of Rdg+Counts)     ±(1.5% + 2)¹
Burden voltage (Typical)     2 mV/mA
DC
Range     400 mA
Resolution     0.1 mA
Accuracy ±(% of Rdg+Counts)     ±(0.2% + 2)
Burden voltage (Typical)     2 mV/mA
Range     60 mA
Resolution     0.01 mA
Accuracy ±(% of Rdg+Counts)     ±(0.2% + 2)
Burden voltage (Typical)     2 mV/mA
Overload     600 mA for 2 minutes maximum
Fuse protection for mA input     0.44 mA, 1000 V, IR 10 kA
AC conversion     Inputs are ac-coupled and calibrated to the rms value of sine wave input
Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3.
¹ 1 kHz bandwidth
Ohms Measurement
Range     Resolution     Accuracy +(% of Rdg+Counts)¹
600.0 Ω     0.1 Ω     ±(0.9% + 2)
6.000 kΩ     0.001 kΩ     ±(0.9% + 2)
60.00 kΩ     0.01 kΩ     ±(0.9% + 2)
600.0 kΩ     0.1 KΩ     ±(0.9% + 2)
6.000 MΩ     0.001 MΩ     ±(0.9% + 2)
50.0 MΩ ²     0.01 MΩ     ±(1.5% + 3)
Overload protection      1000 V rms or dc
Open circuit test voltage      <8.0 V dc
Short circuit current      <1.1 mA
¹ Accuracies apply from 0% to 100% of range
² Up to 80% relative humidity
Diode Test
Diode test indication     Display voltage drop: 0.6 V at1.0 mA nominal test current:
Accuracy     ±(2% + 3)
Continuity Test
Continuity indication     Continuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω
Open circuit voltage     <8.0 V
Short circuit current     1.0 mA typical
Overload protection     1000 V rms
Response time     >1 m sec
Frequency Measurement
Range     Resolution     Accuracy ±(% of Rdg+Counts)
99.99 Hz      0.01 Hz      ±(0.1% + 1)
999.9 Hz      0.1 Hz      ±(0.1% + 1)
9.999 kHz      0.001 kHz      ±(0.1% + 1)
99.99 kHz      0.01 kHz      ±(0.1% + 1)
Frequency Counter Sensitivity
600.0 mV ac      V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz      100.0 mV
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz     150.0 mV
DC Trigger Levels¹ to 20 kHz²     NA
6.0 V      V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz      1.0 V
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz     1.5 V
DC Trigger Levels¹ to 20 kHz²     -400.0 mV and 2.5 V
60.0 V      V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz      10.0 V
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz     36.0 V
DC Trigger Levels¹ to 20 kHz²     1.2 V and 4.0 V
600.0 V      V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz      100.0 V
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz     -
DC Trigger Levels¹ to 20 kHz²     12.0 V and 40.0 V
1000.0 V      V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz      300.0 V
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz     -
DC Trigger Levels¹ to 20 kHz²     12.0 V and 40.0 V
¹ Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy
² Usable to 100 kHz with full scale input
Capacitance
Range      Resolution      Accuracy ±(% of Rdg+Counts)
1000 nF      1 nF     ±(1.2% + 2)
10.00 μF      0.01 μF     ±(1.2% + 2)
100.0 μF      0.1 μF     ±(1.2% ±90 counts)
9999 μF      1 μF     ±(1.2% ±90 counts)
Temperature Measurement
Range      Resolution      Accuracy ±(% of Rdg+Counts)¹
-40 ° C to 537 ° C      0.1 °C      ±(1% + 10 counts)
-40 ° F to 998 ° F      0.1 °F      ±(1% + 18 counts)
¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument
Insulation Specifications
Measurement range     0.01 MΩ to 2 GΩ
Test voltages     50, 100, 250, 500, 1000 V
Test voltage accuracy     +20%, -0%
Short-circuit test current     1 mA nominal
Auto discharge     Discharge time <0.5 second for C = 1 μF or less
Live circuit detection     Inhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive load     Operable with up to 1 μF load
Output Voltage
50 V (0% to +20%)     Display range     0.01 to 6.00 MΩ
Resolution     0.01 MΩ
Test current     1 mA @ 50 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(3% + 5 counts)
Display range     6.0 to 50.0 MΩ
Resolution     0.1 MΩ
Test current     1 mA @ 50 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(3% + 5 counts)
100 V (0% to +20%)     Display range     0.01 to 6.00 MΩ
Resolution     0.01 MΩ
Test current     1 mA @ 100 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(3% + 5 counts)
Display range     6.0 to 60.0 MΩ
Resolution     0.1 MΩ
Test current     1 mA @ 100 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(3% + 5 counts)
Display range     60 to 100 MΩ
Resolution     1 MΩ
Test current     1 mA @ 100 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(3% + 5 counts)
250 V (0% to +20%)     Display range     0.1 to 60.0 MΩ
Resolution     0.1 MΩ
Test current     1 mA @ 250 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(1.5% + 5 counts)
Display range     60 to 250 MΩ
Resolution     1 MΩ
Test current     1 mA @ 250 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(1.5% + 5 counts)
500 V (0% to +20%)     Display range     0.1 to 60.0 MΩ
Resolution     0.1 MΩ
Test current     1 mA @ 500 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(1.5% + 5 counts)
Display range     60 to 500 MΩ
Resolution     1 MΩ
Test current     1 mA @ 500 kΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(1.5% + 5 counts)
1000 V (0% to +20%)     Display range     0.1 to 60.0 MΩ
Resolution     0.1 MΩ
Test current     1 mA @ 1 MΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(1.5% + 5 counts)
Display range     60 to 600 MΩ
Resolution     1 MΩ
Test current     1 mA @ 1 MΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(1.5% + 5 counts)
Display range     0.6 to 2.0 GΩ
Resolution     100 MΩ
Test current     1 mA @ 1 MΩ
Resistance accuracy ±(% of Rdg + Counts)     ±(10% + 3 counts)
General Specifications
Maximum voltage applied to any terminal and common     1000 V
Storage temperature     -40 °C to 60 °C (-40 °F to 140 °F)
Operating temperature     -20 °C to 55 °C (-4 °F to 131 °F)
Temperature coefficient     0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F)
Relative humidity     Noncondensing
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F)
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F)
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F)
Vibration     Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Radio frequency communication     2.4 GHz ISM Band
Radio frequency certification     FCC: T68-FBLE, IC: 6627A-FBLE

size 203 x 100 x 50 mm (with holster)
Power Supply Four AA alkaline batteries
Manufacturer Fluke
MPN 1587 FC
Manufacturer Warranty 3 years
upc code 095969796620
You're reviewing: FLUKE 1587 FC Insulation Multimeter with Fluke Connect
Your Rating