Bierer 83280 Analog Phasing Voltmeter and Voltage Detector 300 Volt - 35kV

$2,859.00
Mitchell Part Number
BIR-83280
Manufacturer
Availability
Typically in stock, Call if Urgent
Quick overview
The 83280 is a unique tool in that it may be used as a conventional phasing meter, or the meter probe may be used as a stand-alone voltage detector on primary or secondary voltages or capacitive test points.

The 83280 has the following features:

  • Can be used as a Stand-Alone Voltage Detector without the Second Probe
  • A Conventional Phasing Meter both Overhead and URD Applications
  • Phase Capacitive Test Points
  • A Large Easy to Read Analog Meter
  • Meter Housing is Completely Shielded to Minimize Stray Field Indications
  • An Insulated (35kV) Interconnect Cable with Second Probe
  • Each Probe is Impact and Water Resistant
  • Meter is Stored in a Highly Durable Padded Carrying Case

The 5-Position Selector Switch Consists of:

  • C - Indicates the Voltage on Capacitive Test Points
  • CP - Phases Using Capacitive Test Points
  • L - Detects Voltage on Overhead and Underground Lines
  • LP - Phases on Overhead and URD Primary Systems
  • BT - Tests Internal Meter Circuitry by Using Internal Battery Voltage, Meter should Deflect Full Scale

Each 83280 Kit comes standard with a straight probe, hook probe, 8ft. interconnect cable, 8ft. extension cable, 3kV power supply, 6VDC battery, instruction manual, padded storage case.

More Information
Weight 40.000000
Product Includes Includes: 300 Volt – 35kV Analog Phasing Voltmeter/Voltage Detector, 8 ft. Regular Cable, 8 ft. Extension Cable, Hook Probe, Straight Probe, 3kV Power Supply, Manual, Case
Specifications

Product Properties:

Shielded Housings, 35Mega Ohm Probes, Self Test Feature in the “T” switch position.

Functional Description:

Standard Phasing Meter, Phase Capacitive Test Points, Stand alone Voltage Detector, Stand alone Capacitive test point Tester, *Hi-Pot URD Cable

Minimum Operating Temperture:

0 degree Fahrenheit (-18 degrees Celsius)

Max. Operating Temperture:

120 degrees Fahrenheit (49 degrees Celsius)

Maximum Operating Range:

16 ft. of Interconnect Cable (4.9 meters)

DC specifications: N/A

AC specifications:

500 volts – 35kV

Physical Dimensions:

Meter Probe, 14.5 in. long (36.8 centimeters) X 4 in. wide (10.2 centimeters) X 7 in. high (17.8 centimeters)

Weight:

2 lbs. (.9 kilograms) Meter Probe, .5 lbs. (.225 kilograms) Second Probe

Applications:

Traditional Phasing on Primary Voltages and Capacitive Test Points. Primary Voltage Detection and Capacitive Test Points.

* Additional accessory required

Manufacturer Bierer
MPN 83280
Manufacturer Warranty 1 Year Warranty Domestic USA; No Warranty for International Shipments
You're reviewing: Bierer 83280 Analog Phasing Voltmeter and Voltage Detector 300 Volt - 35kV